Heading | 04/20/2022 | UNDERGROUND PLUMB | Steven Ramirez | APPROVED | eTRAKiT Inspection Request | 4/19/2022 4:02:42 PM
4/19/2022 4:02 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
4/20/2022 9:40:10 AM
Underground pvc stub in to the building.
|
|
Heading | 06/07/2022 | STRUCTURAL SHEATHING | Daniel Amador | APPROVED W/COND | eTRAKiT Inspection Request | 6/6/2022 4:05:32 PM
6/6/2022 4:05 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
6/7/2022 10:57:16 AM
Don't forget to call fire rated wall inspection.
|
|
Heading | 06/10/2022 | FIRE RATED WALL | Daniel Amador | DENIED | eTRAKiT Inspection Request | 6/6/2022 4:05:31 PM
6/6/2022 4:05 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
6/9/2022 4:03:41 PM
6/9/2022 4:03 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
6/10/2022 11:50:30 AM
"C" track is not over lapping, damaged panel and remove 2X4 all items going up to roof top section. Get specific repair details for this product or have framer repair to plans.
|
|
Heading | 06/13/2022 | HOUSE WRAP | Don Richmond | CANCELLED | eTRAKiT Inspection Request | 6/12/2022 11:30:14 PM
6/12/2022 11:30 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 06/13/2022 | HOUSE WRAP | Don Richmond | APPROVED | eTRAKiT Inspection Request | 6/12/2022 11:29:28 PM
6/12/2022 11:29 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 07/20/2022 | ROUGH ELECTRIC | Chris Papp | APPROVED | eTRAKiT Inspection Request | 7/20/2022 1:05:10 AM
7/20/2022 1:05 AM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 07/21/2022 | ELEC SERVICE/CL | Chris Papp | APPROVED | eTRAKiT Inspection Request | 7/20/2022 5:46:11 PM
7/20/2022 5:46 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 07/21/2022 | GAS METER RELEASE | Steven Ramirez | APPROVED | eTRAKiT Inspection Request | 7/20/2022 5:49:36 PM
7/20/2022 5:49 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 07/21/2022 | GAS PIPING | Steven Ramirez | APPROVED | eTRAKiT Inspection Request | 7/20/2022 5:49:37 PM
7/20/2022 5:49 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/21/2022 9:28:26 AM
Holding pressure at 20 psi.
|
|
Heading | 07/21/2022 | ROUGH HVAC | Steven Ramirez | DENIED | eTRAKiT Inspection Request | 7/20/2022 5:49:38 PM
7/20/2022 5:49 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/21/2022 9:29:41 AM
1. A supply duct in the garage next to the exterior must be a 7 inch, there is a 6 inch installed.
2. On the 2nd floor living room area in the ceiling the Manual D is showing a 7 inch going to the 3rd floor and a 6 inch is installed there now.
3. Install the transfer grill for the laundry room.
4. Any exhaust outlet must be 3 feet above or 10 feet horizontally away from any air intake.
5. Also, can not use the underfloor space as a return air. It must be completely ducted.
|
|
Heading | 07/21/2022 | ROUGH PLUMBING | Steven Ramirez | DENIED | eTRAKiT Inspection Request | 7/20/2022 5:49:37 PM
7/20/2022 5:49 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/21/2022 9:30:06 AM
1. Any exhaust outlet must be 3 feet above or 10 feet horizontally away from any air intake.
|
|
Heading | 07/25/2022 | HOUSE WRAP | Kirk Cadotte | APPROVED | eTRAKiT Inspection Request | 7/22/2022 12:06:38 PM
7/22/2022 12:06 PM LINCO ENTERPRISES LLC
Lath Inspection
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/25/2022 8:11:45 AM
Lath inspection. Approved
|
|
Heading | 07/25/2022 | ROUGH HVAC | Steven Ramirez | DENIED | eTRAKiT Inspection Request | 7/22/2022 12:18:58 PM
7/22/2022 12:18 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/25/2022 8:03:13 AM
House locked. Outside corrections not made from previous inspection. All corrections must be made prior to requesting a reinspection.
|
|
Heading | 07/25/2022 | ROUGH PLUMBING | Steven Ramirez | DENIED | eTRAKiT Inspection Request | 7/22/2022 12:18:58 PM
7/22/2022 12:18 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/25/2022 8:03:24 AM
House locked. Outside corrections not made from previous inspection. All corrections must be made prior to requesting a reinspection.
|
|
Heading | 07/26/2022 | ROUGH FRAMING | Daniel Amador | CANCELLED | eTRAKiT Inspection Request | 7/25/2022 3:05:19 PM
7/25/2022 3:05 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 07/28/2022 | FIRE RATED WALL | Daniel Amador | APPROVED W/COND | eTRAKiT Inspection Request | 7/26/2022 5:00:01 PM
7/26/2022 4:59 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/28/2022 9:54:39 AM
Pending city approval for material and UL listing that is being used on site. This material was not approved on plans.
|
|
Heading | 07/28/2022 | ROUGH FRAMING | Daniel Amador | DENIED | eTRAKiT Inspection Request | 7/26/2022 5:00:01 PM
7/26/2022 4:59 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/28/2022 9:53:03 AM
Must pass all MEP's prior to rough frame
|
|
Heading | 07/29/2022 | ROUGH FRAMING | Frank Goodard | DENIED | eTRAKiT Inspection Request | 7/28/2022 9:29:37 PM
7/28/2022 9:29 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/29/2022 11:18:46 AM
1. Must pass all MEPs prior to rough frame.
2. Missing Anchor bolts.
3. Fire block drop ceiling at mech. room and main level bath.
4. Missing anchor bolts at HSS 5x4x1/2 post in garage.
5. Secure ladder at crawl space.
6. Fire block at stair stringers.
7. Weld all tabs at mono post.
8. Need approved truss cals.
9 Not ready incomplete inspection.
|
|
Heading | 07/29/2022 | ROUGH HVAC | Brad Umbarger | APPROVED W/COND | eTRAKiT Inspection Request | 7/28/2022 9:29:38 PM
7/28/2022 9:29 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
7/29/2022 12:29:46 PM
Will need to finish covering all of the wood for the floor joist flanges with metal ducting on the inside of the return bays. We can check this at final inspection.
|
|
Heading | 07/29/2022 | ROUGH PLUMBING | Brad Umbarger | APPROVED | eTRAKiT Inspection Request | 7/28/2022 9:29:38 PM
7/28/2022 9:29 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 08/01/2022 | ROUGH FRAMING | Daniel Amador | DENIED | eTRAKiT Inspection Request | 7/31/2022 12:39:14 PM
7/31/2022 12:39 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
8/1/2022 10:36:05 AM
1) still need to weld monos to beams, check all
2) truss joist missing mid span bracing, refer to truss pack
3) missing air barriers on exterior dead space walls in bathroom on third level
ok to insulate
|
|
Heading | 08/10/2022 | INSULATION | Daniel Amador | DENIED | eTRAKiT Inspection Request | 8/9/2022 9:56:49 AM
8/9/2022 9:56 AM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
8/10/2022 10:10:23 AM
still missing air barriers at showers
|
|
Heading | 08/10/2022 | ROUGH FRAMING | Daniel Amador | DENIED | eTRAKiT Inspection Request | 8/9/2022 9:56:49 AM
8/9/2022 9:56 AM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
8/10/2022 10:15:06 AM
monos still not welded on first level
|
|
Heading | 08/11/2022 | ROUGH FRAMING | Daniel Amador | APPROVED | eTRAKiT Inspection Request | 8/10/2022 8:45:12 PM
8/10/2022 8:45 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 08/18/2022 | DRYWALL | Daniel Amador | DENIED | eTRAKiT Inspection Request | 8/17/2022 11:58:21 PM
8/17/2022 11:58 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
8/18/2022 8:33:40 AM
Insulation item not done.
|
|
Heading | 08/18/2022 | INSULATION | Daniel Amador | DENIED | eTRAKiT Inspection Request | 8/17/2022 11:58:21 PM
8/17/2022 11:58 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
8/18/2022 8:34:36 AM
Unable to verify air barrier
|
|
Heading | 08/19/2022 | DRYWALL | Daniel Amador | APPROVED | eTRAKiT Inspection Request | 8/18/2022 10:20:23 PM
8/18/2022 10:20 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 08/19/2022 | INSULATION | Daniel Amador | APPROVED | eTRAKiT Inspection Request | 8/18/2022 10:20:24 PM
8/18/2022 10:20 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 08/26/2022 | SHOWER PAN | Frank Goodard | APPROVED | eTRAKiT Inspection Request | 8/25/2022 11:01:06 AM
8/25/2022 11:01 AM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 10/06/2022 | CO-PUBLIC IMPROVMNT | Spencer Greason | APPROVED | CO Public Improvements | 10/5/2022 3:16:51 PM
10/5/2022 3:16 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
10/6/2022 3:29:30 PM
Water and Sewer services are good.
Asphalt, C&G and Sidewalk are good.
All work inspected is approved per CoA Standards.
|
|
Heading | 10/06/2022 | FINAL ELECTRICAL** | Chris Papp | APPROVED | eTRAKiT Inspection Request | 10/5/2022 3:16:51 PM
10/5/2022 3:16 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 10/06/2022 | FINAL HVAC** | Steven Ramirez | DENIED | eTRAKiT Inspection Request | 10/5/2022 3:16:51 PM
10/5/2022 3:16 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
10/6/2022 8:10:16 AM
Incomplete. Gas meters not installed. No inspection until the work is 100% complete. Check the furnace air intake an exhaust outside of the house.
|
|
Heading | 10/06/2022 | FINAL PLUMBING** | Steven Ramirez | DENIED | eTRAKiT Inspection Request | 10/5/2022 3:16:52 PM
10/5/2022 3:16 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
10/6/2022 8:10:41 AM
Incomplete. No inspection. Gas meter not installed.
|
|
Heading | 10/06/2022 | FINAL STRUCTURAL** | Frank Goodard | DENIED | eTRAKiT Inspection Request | 10/5/2022 3:16:52 PM
10/5/2022 3:16 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
10/6/2022 2:10:05 PM
1. Remove insulation or finish 2nd floor patio ceiling.
2. Post address numbers.
Seal penetrations in garage ceiling.
|
|
Heading | 10/07/2022 | FINAL HVAC** | Brad Umbarger | APPROVED | eTRAKiT Inspection Request | 10/6/2022 7:46:02 PM
10/6/2022 7:46 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 10/07/2022 | FINAL PLUMBING** | Brad Umbarger | APPROVED | eTRAKiT Inspection Request | 10/6/2022 7:46:02 PM
10/6/2022 7:46 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 10/07/2022 | FINAL STRUCTURAL** | Brad Umbarger | DENIED | eTRAKiT Inspection Request | 10/6/2022 7:46:03 PM
10/6/2022 7:46 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
10/7/2022 8:46:35 AM
Corrections not completed.
|
|
Heading | 10/10/2022 | FINAL STRUCTURAL** | Frank Goodard | APPROVED | eTRAKiT Inspection Request | 10/7/2022 1:18:41 PM
10/7/2022 1:18 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | 10/11/2022 | CO/TCO | Dixielee Rodriguez | DENIED | eTRAKiT Inspection Request | 10/10/2022 3:38:26 PM
10/10/2022 3:38 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
10/11/2022 4:25:31 PM
NEED ENERGY CERT UPLOADED AND PLEASE ADDRESS KYLEY'S COMMENTS FROM HER REVIEW ON 8/2/2022.
THANK YOU
|
|
Heading | 10/12/2022 | CO/TCO | Dixielee Rodriguez | DENIED | eTRAKiT Inspection Request | 10/11/2022 11:44:36 PM
10/11/2022 11:44 PM LINCO ENTERPRISES LLC
Prescriptive method was used so energy cert not required. Insulation cert was previously uploaded. Sent Kyley an email addressing her comments
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
10/12/2022 12:06:18 PM
KYLEY'S REVIEW NEEDS TO BE APPROVED BEFORE WE CAN SET UP CO/TCO APPROVAL REVIEWS.
|
|
Heading | 10/14/2022 | CO/TCO | Dixielee Rodriguez | ACCEPTED | eTRAKiT Inspection Request | 10/13/2022 1:43:34 PM
10/13/2022 1:43 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | | ROUGH HVAC | Kirk Cadotte | | eTRAKiT Inspection Request | 7/26/2022 5:00:00 PM
7/26/2022 4:59 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|
Heading | | ROUGH PLUMBING | Kirk Cadotte | | eTRAKiT Inspection Request | 7/26/2022 5:00:00 PM
7/26/2022 4:59 PM LINCO ENTERPRISES LLC
Contact Name: LINCO ENTERPRISES LLC
Site Address: 8500 W 62ND AVE G
Phone: 7202539999
e-Mail: [email protected]
|
|